Customization: | Available |
---|---|
Application: | High-performance Transducer, Three Phase Transducer, General Transducer, Single-phase Transducer, High Frequency Converter Transducer |
Output Type: | Triple |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
The 1769 Compact I/O modules can be fine-tuned with the provided parameters such as process alarms, input filters, real time sampling, alarm deadband and others. When a channel is enabled, the internal open-circuit detection is automatically enabled. This open circuit detection also activates the under-range error bit of the module. When the errors are detected by the module, it can be made known to the controller and display a non-fatal system error which may be further linked to a monitoring system such as a Human Machine Interface (HMI) or Supervisory Control and Data Acquisition (SCADA). The 1769-IF4 is a Compact I/O analog module. It can convert and store the analog data digitally. Four differential or single-ended channels are available for this module and it can perform auto-calibration when it is enabled initially in a channel or when the channel has a different configuration than that of the previous channel. Note that this module does not provide loop power for analog inputs and that it is necessary to have a power supply that matches the input transmitter's specifications. The user can wire the 1769-IF4 module's channels as single-ended or differential inputs. The 1769-IF4 also has a common mode rejection ratio that is greater than 60 dB and a normal mode rejection ratio of -50 dB at 50 to 60 Hertz. It has an open-type enclosure and it can be mounted on a DIN rail or panel mount. The connection cables compatible with the 1769-IF4 are 22-14 AWG solid and 22-16 AWG stranded. This module also comes with an LED status indicator and measures 87 x 35 x 118 millimeters. The 1769-IF4 has input ranges of +/-10 Volts, 0 to 10 Volts, 0 to 5 Volts, 1 to 5 Volts, 0 to 20 mA, and 4 to 20 mA. Its maximum current draw is 5 Volts DC for both Series A and Series B modules and 24 Volts DC for Series B modules. The rated working voltage is 30 Volts AC or DC and the common mode voltage range is +/-10 Volts maximum per channel. The storage temperature requirement of the 1769-IF4 is -40 to 85 degrees Celsius, while its operating temperature is 0 to 60 degrees Celsius. The module's operating vibration is 5 g at 10 to 500 Hertz and a relay operating vibration of 2 g while s operating shock is 30 g, non-operating shock is 40 g, and relay operation shock is 7.5 g. It also has a 2000-meter operating altitude and a non-condensing relative humidity of 5 to 95%.
Part Number/Catalog No. | 1769-IF4 |
---|---|
Product Line | CompactLogix |
Module Type | 4 Channel Analog Input Module |
Input Type | Analog Input |
Product Type | Analog Input Module |
Compatible Controllers: | MicroLogix 1500; 1769 CompactLogix |
Communication Cable | 4 Point |
No. of Inputs: | 4 Differential and Single Ended Inputs |
Power Supply Distance rating: | 8 |
Shipping Weight | 2 lbs. |
Shipping Dimensions | 8X8X5 in. |
Input current range: | 0-21 mA |
Series | A and B |
Current signal normal ranges: | 0-20mA; 4-20 mA |
Converter Type | Delta Sigma |
Current signal full range: | 0-21 mA; 3.2 - 21 mA. |
Input voltage range: | 0-10.5VDC |
Backplane Current | 1.4 Amps at 24 Volts |
Voltage signal normal ranges: | ±10V DC, 0 …10V DC, 0…5V DC, 1…5V DC |
Power Consumption | 33.6 Watts |
Voltage signal full range: | ±10.5V DC, -0.5…10.5V DC, -0.5…5.25V DC, 0.5…5.25V DC |
External Power Switch | 24 VDC |
Power Dissipation | 7.5 Watts |
Resolution: | 14 bits (unipolar) 14 bits plus sign (bipolar) |