Customization: | Available |
---|---|
Task: | Adjust |
Structure: | Combination |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Range of Product | Modicon X80 |
---|---|
Product or Component Type | Discrete output module |
Product Specific Application | For severe environments |
Discrete output number | 32 EN/IEC 61131-2 |
Discrete output type | Solid state |
Discrete output logic | Positive |
Discrete output voltage | 24 V 19...30 V DC |
Discrete output current | 0.1 A |
Current per channel | 0.125 A |
Maximum current per module | 3.2 A |
Maximum leakage current | 0.1 mA at state 0 |
Maximum voltage drop | <1.5 V at state 1 |
Insulation resistance | > 10 MOhm 500 V DC |
Power dissipation in W | 3.6 W |
Response time on output | 1.2 ms |
Paralleling of outputs | Yes : 3 maximum |
Typical current consumption | 125 mA 3.3 V DC |
MTBF reliability | 290000 H |
Protection type | reverse polarity protection External short-circuit protection overload protection overvoltage protection |
Output overload protection | With current limiter With electronic circuit breaker 0.125 A < Id < 0.185 A |
Output overvoltage protection | With transil diode |
Output short-circuit protection | With 2 A external fuse |
Reverse polarity protection | Reverse mounted diode |
Voltage detection threshold | < 14 V DC preactuator fault > 18 V DC preactuator at state 0 |
Maximum tungsten load | 1.2 W |
Switching frequency | 0.5/LI² Hz |
Maximum overload time | 15 ms |
Load impedance ohmic | >= 220 Ohm |
Status LED | 1 LED (Green) module operating (RUN) 1 LED per channel (Green) channel diagnostic 1 LED (Red) module error (ERR) 1 LED (Red) module I/O |
Net Weight | 0.24 lb(US) (0.11 kg) |